Products/EOCR-iF — Ground Fault Relay ดิจิทัล/IFMZ-WRCUWZ

Samwha EOCR
IFMZ-WRCUWZ
EOCR-iFMZ (i-Series, ground fault)
รุ่นย่อย: ช่วงกระแส 0.5–60 A (direct) · ไฟเลี้ยง 100–240 V AC/DC (85–110 %, free voltage) · แบบร้อยสายผ่านรู (Window) — มีฟังก์ชันตรวจไฟรั่วลงดิน (GF) และสื่อสาร Modbus RS-485
ดาวน์โหลดเอกสารDOWNLOADMain Feature
- ▪ Integrated model with improved functions over the FMZ series it replaces
- ▪ Ground-fault (GF) protection with earth-leakage current display
- ▪ Modbus RS-485 communication
- ▪ Supports definite, inverse and thermal inverse time characteristics
- ▪ RoHS compliant
Protection functions
- ▪ Over current (OC), In > OC setting
- ▪ Under current (UC)
- ▪ Ground fault (GF) — leakage current measured and displayed
- ▪ Phase loss, phase reversal
- ▪ Locked rotor (stall / jam)
- ▪ Current imbalance
Technical Specification
| This variant | ||
| Model | IFMZ-WRCUWZ | |
| Current range | 0.5–60 A (direct) | |
| Output contact type | C — b(95-96), a(97-98): OC and GR common | |
| Control voltage | 100–240 V AC/DC (85–110 %, free voltage) | |
| CT type | Window type (flush mounting) | |
| Protection settings | ||
| Over current rated setting range | 0.5–60 A (definite TCC; use external CT above 60 A) | |
| Over current rated setting range | 0.5–32 A (inverse and thermal TCC) | |
| Under current rated setting range | 0.5 A – less than OC setting | |
| Operating time characteristics | definite (Def) / inverse (Inv) / thermal (th) | |
| Definite D-time | 0–200 s | |
| Definite O-time | 0.2–30 s | |
| Inverse and thermal (cLS) | 1–30 classes | |
| GF delay time (Edt) | 0–30 s | |
| GF O-time (Et) | 0.05–10 s | |
| Auto-reset | 0.5 s – 20 min | |
| Reset mode | manual (H-r) / electric (E-r) / auto (A-r) | |
| Control power and output | ||
| Control power voltage | 100–240 V AC/DC (85–110 %, free voltage), 24 V AC/DC (±5 %) | |
| Frequency | 50/60 Hz | |
| Power consumption | lower than 7 VA | |
| Output capacity | 3 A / 250 V AC resistive | |
| Output composition | 1a — GR (iFMZ) | |
| Communication | Modbus / RS-485 | |
| Display and mounting | ||
| Display | 5-digit 7-segment LED — 3-phase amps, cause of trip, setting parameters | |
| Bar graph | load factor versus OC setting (minimum scale 65 %) | |
| Current display | 3-phase load currents and leakage current shown in sequence every 2 seconds | |
| Mounting | flush mounting (iFMZ) | |
| Dimension window type | 70 W × 74.5 H × 83.8 D mm | |
| Dimension bottom hole type | 70 W × 56.3 H × 108.1 D mm | |
| Insulation and EMC | ||
| Insulation between case and circuit | over DC 500 V, 10 MΩ | |
| Dielectric strength | 2 kV case-circuit, 1 kV between contacts, 2 kV between circuit (50/60 Hz, 1 min) | |
| Electrostatic discharge | IEC 61000-4-2 level 3, air ±8 kV, contact ±6 kV | |
| Radiated disturbance | IEC 61000-4-3 level 3, 10 V/m, 80–1000 MHz | |
| Conducted disturbance | IEC 61000-4-6 level 3, 10 V, 0.15–80 MHz | |
| EFT / burst | IEC 61000-4-4 level 3, ±2 kV, 1 min | |
| Surge | IEC 61000-4-5 level 3, 1.2 × 50 µs, ±4 kV | |
| Emission | CISPR11 class A (conducted and radiated) | |
| Environment | ||
| Storage temperature | -40 … +85 °C | |
| Operating temperature | -20 … +60 °C | |
| Humidity | 30–85 % RH (non-condensate) | |
| Ordering code (iFMZ - WR / D / U / W / Q) | ||
| Current range | WR = 0.5–60 A; H1 = 100:5, HH = 150:5, H2 = 200:5, H3 = 300:5, H4 = 400:5 (3CT combination type) | |
| Output contact type | A, C or D (see specification above) | |
| Control voltage | B = 24 V AC/DC, U = 100–240 V AC/DC | |
| CT type | W = window, H = bottom hole, T = terminal | |
ข้อมูลตามเอกสารผู้ผลิต (Samwha EOCR) — รายละเอียดฉบับเต็มดูจาก Datasheet ด้านล่าง
📥 Downloads — เอกสารสำหรับขออนุมัติโครงการ
รุ่นที่เกี่ยวข้อง
ดูรุ่นทั้งหมดในกลุ่มนี้ที่ EOCR-iF — Ground Fault Relay ดิจิทัล
อ่านก่อนเลือกรุ่น
- มอเตอร์ทริปเพราะไฟรั่วลงดิน (Ground Fault) — สาเหตุและการตรวจ
อาการทริปจากไฟรั่วลงดิน (Ground Fault / Earth Leakage) เกิดจากฉนวนเสื่อมหรือความชื้น ตรวจจับด้วย ZCT ร่วมกับ Ground Fault Relay บทความนี้อธิบายสาเหตุ วิธีตรวจ และอุปกรณ์ที่เกี่ยวข้อง
- ZCT (Zero-phase Current Transformer) คืออะไร ทำงานอย่างไร
ZCT คืออะไร หลักการทำงานตรวจจับไฟรั่วลงดิน ต่างจาก CT ทั่วไปอย่างไร ต้องให้สายเส้นใดลอดผ่านบ้าง และใช้ร่วมกับ Ground Fault Relay อย่างไร
- การติดตั้ง ZCT ที่ถูกต้อง: สายไหนต้องร้อยผ่าน สายไหนห้าม
วิธีติดตั้ง ZCT ให้ตรวจไฟรั่วได้จริง: สายเฟสทุกเส้น (และนิวทรัลถ้ามี) ต้องร้อยผ่านรูทิศทางเดียวกัน ห้ามร้อยสายดิน/PE เด็ดขาด พร้อมวิธีจัดการ Shield ของสายชีลด์ และข้อผิดพลาดหน้างานที่พบบ่อย
- วิธีเลือกขนาด ZCT: วัดจากกระแสหรือขนาดรู?
วิธีเลือก ZCT ให้ถูก — ไม่ได้เลือกจากกระแสโหลดเหมือน CT แต่ดูจากชนิดรีเลย์ ความเข้ากันได้ของเอาต์พุต ขนาดรู จำนวนสายและ Cable OD รวม ระยะติดตั้ง และข้อกำหนดผู้ผลิต